Dual-Flange Level Transmitters under High-Temperature and Vacuum Working Conditions

Dual-Flange Level Transmitters under High-Temperature and Vacuum Working Conditions

Among all field conditions, the combination of high temperature and strong vacuum is one of the most demanding challenges for the remote diaphragm seal system. The filling fluid sealed inside the diaphragm, capillary and sensor chamber must transmit process pressure reliably while enduring sustained high temperature and negative pressure at the same time. High temperature accelerates vaporization and oxidation of conventional filling fluids, whereas vacuum lowers the boiling point and promotes outgassing; jointly they easily generate bubbles inside the sealing circuit, interrupt pressure transmission and cause serious drift or complete loss of measurement. This article analyzes the failure mechanism of dual-flange transmitters under combined high-temperature and vacuum conditions, examines the influence of filling fluid type, diaphragm material, capillary length and installation practice, and proposes systematic selection and installation guidelines for long-term stable and accurate level measurement.
Keywords: dual-flange level transmitter; remote diaphragm seal; filling fluid; high temperature; vacuum; silicone oil; fluorinated oil; measurement drift
  1. Introduction

A dual-flange level transmitter measures liquid level through the hydrostatic pressure difference between the upper and lower flanges connected by sealed capillaries. The two flanges mount at the high and low level points of a vessel, and the filling fluid transmits the pressure to the differential pressure sensing element. When the process medium is at high temperature, the whole seal assembly is heated as well. When the process runs under vacuum, the absolute pressure inside the vessel drops significantly. The most severe case is that a single process combines both high temperature and vacuum, such as distillation columns, vacuum reactors, hot oil degassing vessels and certain thermal process tanks. Under such conditions, the filling fluid becomes the decisive factor between reliable measurement and frequent field failure.
  1. Failure Mechanism under High Temperature and Vacuum

The fundamental problem is the physical state change of the filling fluid. All organic filling fluids have a certain saturated vapor pressure, which rises rapidly with temperature. When the process temperature exceeds the boiling point corresponding to the current absolute pressure, the filling fluid begins to vaporize and produces bubbles inside the diaphragm cavity and the capillary. Once bubbles form, the fluid column is no longer continuous, pressure transmission is interrupted, and the level reading becomes unstable, jumps periodically or even drops to zero.
Vacuum aggravates this process. Under negative pressure, the boiling point of the filling fluid is significantly lowered, so vaporization occurs at a much lower temperature than at atmospheric pressure. In a high-temperature and vacuum combined condition, ordinary silicone oil can easily reach its vaporization threshold, resulting in rapid bubble formation and severe measurement failure. Meanwhile, dissolved gas inside the filling fluid may also escape under vacuum, further creating bubbles. Thermal expansion is another contributor. High temperature expands the filling fluid volume and creates extra pressure on the diaphragm, causing zero drift that changes with process temperature. Oxidation at high temperature gradually degrades the fluid, alters its viscosity and thermal expansion coefficient, and shortens the service life of the whole seal system.
  1. Selection of Filling Fluid

The most critical decision is the selection of the filling fluid. Standard silicone oil is suitable for general temperature applications around -40 to 205 degrees Celsius at atmospheric pressure, but it is not recommended for combined high-temperature and vacuum service. High-temperature silicone oil, such as the DC704 grade, extends the working temperature range up to about 315 degrees Celsius and features much lower saturated vapor pressure and better thermal oxidation resistance. It tolerates thermal cycling well and is less likely to vaporize. For processes that combine high temperature with strong vacuum, special filling fluids such as fluorinated oil are often required. Fluorinated filling fluids offer extremely low vapor pressure, outstanding chemical inertness and high-temperature stability, making them the preferred choice for the most demanding vacuum service.
  1. Diaphragm and Structural Considerations

The diaphragm material must resist corrosion from the measured medium at high temperature. Common materials include 316L stainless steel, Hastelloy C, tantalum and gold-plated variants, selected according to medium compatibility and temperature rating. At high temperature, metal creep and thermal expansion of the diaphragm may introduce additional measurement errors, so diaphragm thickness and rigidity should be matched to the rated pressure. Capillary length also affects response speed and temperature error. Longer capillaries increase thermal expansion volume and slow down pressure transmission, so the capillary should be as short as possible and should be routed away from heat sources. Ambient temperature fluctuation along the capillary changes the density of the filling fluid and introduces additional zero shift, which is especially noticeable in vacuum service where the measurement span is small. Heat tracing and thermal insulation of the capillaries are often necessary to keep the filling fluid temperature stable.
  1. Installation and Calibration

Proper installation reduces the risk of failure. The high and low pressure flanges should be mounted at the correct level points, and the transmitter should be located to minimize the influence of ambient temperature. The filling system must be completely degassed during manufacturing; any remaining dissolved gas will separate into bubbles under high-temperature vacuum operation. Before commissioning, zero calibration and range verification should be performed at the actual process temperature and pressure. In service, regular monitoring of zero point stability can detect early signs of filling fluid degradation or bubble formation, allowing preventive maintenance before total failure.
  1. Conclusion

The combined high-temperature and vacuum working condition is a severe test for dual-flange level transmitters. The root cause of most failures is the physical state change of the filling fluid, which vaporizes and forms bubbles that interrupt pressure transmission. Correct selection of the filling fluid is the most important step: standard silicone oil for normal conditions, high-temperature silicone oil for high temperature, and fluorinated oil for combined high-temperature and strong vacuum service. Diaphragm material, capillary layout, heat tracing and complete degassing during filling also play key roles. With proper selection, installation and calibration, dual-flange level transmitters can provide long-term stable and accurate level measurement even in the most demanding high-temperature vacuum processes.
Dual-Flange Level Transmitters under High-Temperature and Vacuum Working Conditions - Kiel Planck
Dual-Flange Level Transmitters under High-Temperature and Vacuum Working Conditions - Kiel Planck

Scan the QR code to receive more detailed information.

Dual-Flange Level Transmitters under High-Temperature and Vacuum Working Conditions - Kiel Planck
Dual-Flange Level Transmitters under High-Temperature and Vacuum Working Conditions - Kiel Planck

Share:

More Posts

Vortex Flow Meters for Saturated Steam Metering - Kiel Planck

Vortex Flow Meters for Saturated Steam Metering

Vortex Flow Meters for Saturated Steam MeteringHowever, a common field problem is the empty pipe or partially filled condition, when the measuring tube is not completely full of liquid. In this state, the conventional two-electrode sensor cannot produce a reliable signal, and the meter may output false flow values that corrupt accounting and mislead process control.

Send Us A Message

captcha
Reload

Bitte geben Sie die im CAPTCHA angezeigten Zeichen ein, um sicherzustellen, dass Sie ein Mensch sind.

Email
Email: info@kielplanckprc.com
WhatsApp
WhatsApp Me