How to Select Capillary Length for a DP Level Transmitter

How to Select Capillary Length for a DP Level Transmitter

Introduction

Remote diaphragm seal differential pressure transmitters are widely used for level measurement in closed vessels and separators.

The two diaphragm seals are connected to the transmitter through capillaries.

Selecting the correct capillary length is important because capillary design can affect measurement response and accuracy.

1. Measure the Actual Installation Distance

Do not select capillary length based only on the straight-line distance between the transmitter and the process connections.

Consider the actual routing path, including:

  • Vertical distance

  • Horizontal distance

  • Pipe and equipment obstacles

  • Cable tray or support locations

  • Maintenance access

  • Required bending allowance

The selected length should provide sufficient routing allowance without unnecessary excess.

2. Avoid Unnecessarily Long Capillaries

Longer capillaries may increase the influence of ambient temperature changes and can affect response time.

They may also make installation and protection more difficult.

Therefore, use the shortest practical length that satisfies the installation layout and manufacturer requirements.

3. Consider Elevation Differences

The elevation difference between the two seals and the transmitter is important.

The filling fluid inside each capillary can create hydrostatic effects.

For differential pressure measurement, unequal elevation or temperature conditions may introduce additional measurement errors.

The instrument configuration and calibration must account for the actual installation arrangement.

4. Consider Ambient Temperature

Capillary filling fluid is affected by temperature.

Different temperatures along the high- and low-pressure capillaries can create unequal effects.

Avoid placing one capillary near a heat source while the other is exposed to a significantly different environment, where possible.

5. Confirm the Filling Fluid

The filling fluid must be suitable for:

  • Process temperature

  • Ambient temperature

  • Minimum pressure conditions

  • Required response time

  • Chemical and safety requirements

Vacuum applications require particular attention to filling fluid vapor pressure.

6. What Information Should Be Given to the Supplier?

Provide:

  1. Separator dimensions

  2. High- and low-pressure tap elevations

  3. Transmitter installation position

  4. Required capillary routing distance

  5. Process temperature

  6. Ambient temperature range

  7. Operating pressure and differential pressure range

Conclusion

Capillary length should be determined by the actual installation layout and measurement conditions, not by guesswork.

Correct routing, elevation compensation, filling fluid selection, and temperature management help improve the reliability of remote seal differential pressure measurement.

How to Select Capillary Length for a DP Level Transmitter - Kiel Planck
How to Select Capillary Length for a DP Level Transmitter - Kiel Planck

Scan the QR code to receive more detailed information.

How to Select Capillary Length for a DP Level Transmitter - Kiel Planck
How to Select Capillary Length for a DP Level Transmitter - Kiel Planck

Share:

More Posts

Send Us A Message

captcha
Reload

Bitte geben Sie die im CAPTCHA angezeigten Zeichen ein, um sicherzustellen, dass Sie ein Mensch sind.

Email
Email: info@kielplanckprc.com
WhatsApp
WhatsApp Me